All the major Government published documents describing methods of designing buildings to safeguard life in buildings in the event of fire:  [[Structural_fire_resistance_requirements#Approved_Document_B|Approved Document B]]<ref name="No1">[https://assets.publishing.service.gov.uk/government/uploads/system/uploads/attachment_data/file/937932/ADB_Vol2_Buildings_other_than_dwellings_2019_edition_inc_2020_amendments.pdf Approved Document B (Fire safety, Volume 2 – Buildings other than Dwellings), 2019 edition incorporating 2020 amendments – for use in England . Ministry of Housing, Communities & Local Government]</ref>; [[Structural_fire_resistance_requirements#Technical_Handbook_2|Scottish Technical Handbook 2]]<ref name="No2">[https://www.gov.scot/publications/building-standards-technical-handbook-2019-non-domestic/ Building standards technical handbook: 2019 – Non-domestic, Section 2 – Fire, The Scottish Government]</ref> and [[Structural_fire_resistance_requirements#Technical_Booklet_E|Technical Booklet E]]<ref name="No3">[https://www.finance-ni.gov.uk/sites/default/files/publications/dfp/Technical-booklet-E-Fire-Safety-October-2012_0.pdf Technical Booklet E, Fire safety, Building Regulations (Northern Ireland) 2012, Department of Finance and Personnel of the Northern Ireland Government, 2012]</ref> in Northern Ireland  allow the use of life safety sprinklers in buildings. In some instances, the use of life safety sprinklers is mandatory. [[Structural_fire_resistance_requirements#BS_9999|BS 9999]]<ref name="No4">BS 9999: 2017, Fire safety in the design, management and use of buildings - Code of practice. BSI</ref> also makes provision for their use. Note that, since 2014, a [[Fire_and_steel_construction#The_Building_Regulations_and_fire_precautions_in_buildings|separate version of Approved Document B has existed for Wales]].  
+
All the major Government published documents describing methods of designing buildings to safeguard life in buildings in the event of fire:  [[Structural_fire_resistance_requirements#Approved_Document_B|Approved Document B]]<ref name="No1">[https://assets.publishing.service.gov.uk/government/uploads/system/uploads/attachment_data/file/937932/ADB_Vol2_Buildings_other_than_dwellings_2019_edition_inc_2020_amendments.pdf Approved Document B (Fire safety, Volume 2 – Buildings other than Dwellings), 2019 edition incorporating 2020 amendments – for use in England . Ministry of Housing, Communities & Local Government]</ref>; [[Structural_fire_resistance_requirements#Technical_Handbook_2022|Scottish Technical Handbook 2022]]<ref name="No2">[https://www.gov.scot/publications/building-standards-2022-technical-handbook-non-domestic/ Building standards technical handbook: 2022 – Non-domestic, Section 2 – Fire, The Scottish Government]</ref> and [[Structural_fire_resistance_requirements#Technical_Booklet_E|Technical Booklet E]]<ref name="No3">[https://www.finance-ni.gov.uk/sites/default/files/publications/dfp/Technical-booklet-E-Fire-Safety-October-2012_0.pdf Technical Booklet E, Fire safety, Building Regulations (Northern Ireland) 2012, Department of Finance and Personnel of the Northern Ireland Government, 2012]</ref> in Northern Ireland  allow the use of life safety sprinklers in buildings. In some instances, the use of life safety sprinklers is mandatory. [[Structural_fire_resistance_requirements#BS_9999|BS 9999]]<ref name="No4">BS 9999: 2017, Fire safety in the design, management and use of buildings - Code of practice. BSI</ref> also makes provision for their use. Note that, since 2014, a [[Fire_and_steel_construction#The_Building_Regulations_and_fire_precautions_in_buildings|separate version of Approved Document B has existed for Wales]].  
  
Where sprinklers operate on the exploding bulb principle, the sprinkler head activates when the fluid expands under the effects of rising temperatures and breaks the glass. Only the sprinklers in the vicinity of the fire are activated. The great majority of fires are controlled by the activation of four or less heads. Further information on the operating principles for automatic sprinklers and their efficiency at controlling and extinguishing fires can be found at the [https://www.bafsa.org.uk/ British Automatic Fire Sprinkler Association] website.  
+
Where sprinklers operate on the exploding bulb principle, the sprinkler head activates when the fluid expands under the effects of rising temperatures and breaks the glass. Only the sprinklers in the vicinity of the fire are activated. Around 60% of fires are supressed by the activation of no more than four sprinkler heads. Further information on the operating principles for automatic sprinklers and their efficiency at controlling and extinguishing fires can be found at the [https://www.bafsa.org.uk/ British Automatic Fire Sprinkler Association] website.  
 
<gallery wrap=true style="float:right;" widths=200px heights=300px>  
 
<gallery wrap=true style="float:right;" widths=200px heights=300px>  
 
Image:Sprinkler_1.png  
 
Image:Sprinkler_1.png  
Line 8: Line 8:
 
</gallery>
 
</gallery>
 
==Sprinklers in UK fire codes and standards==
 
==Sprinklers in UK fire codes and standards==
The emphasis placed on the use of sprinklers in buildings in fire codes and standards varies between [[Structural_fire_resistance_requirements#Approved_Document_B|Approved Document B]]<ref name="No1"></ref>; [[Structural_fire_resistance_requirements#Technical_Handbook_2|Scottish Technical Handbook 2]] <ref name="No2"></ref>,  [[Structural_fire_resistance_requirements#Technical_Booklet_E|Technical Booklet E]]<ref name="No3"></ref>  and  [[Structural_fire_resistance_requirements#BS_9999|BS 9999]]<ref name="No4"></ref>.
+
The emphasis placed on the use of sprinklers in buildings in fire codes and standards varies between [[Structural_fire_resistance_requirements#Approved_Document_B|Approved Document B]]<ref name="No1"></ref>; [[Structural_fire_resistance_requirements#Technical_Handbook_2022|Scottish Technical Handbook 2022]] <ref name="No2"></ref>,  [[Structural_fire_resistance_requirements#Technical_Booklet_E|Technical Booklet E]]<ref name="No3"></ref>  and  [[Structural_fire_resistance_requirements#BS_9999|BS 9999]]<ref name="No4"></ref>.
  
For dwellings and residential buildings, guidance on the installation of life safety sprinklers is given in BS 9251<ref name="No5"> BS 9251:2014 Sprinkler systems for residential and domestic occupancies – Code of practice. BSI</ref>. For non-residential buildings or dwellings and residential buildings outside the scope of BS 9251<ref name="No5"></ref>, the requirements of BS EN 12845<ref name="No6">BS EN 12845:2015+A1:2019 Fixed fire-fighting systems. Automatic sprinkler systems. Design, installation and maintenance. BSI</ref> should be followed.
+
For dwellings and residential buildings, guidance on the installation of life safety sprinklers is given in BS 9251<ref name="No5"> BS 9251:2021 Sprinkler systems for residential and domestic occupancies – Code of practice. BSI</ref>. For non-residential buildings or dwellings and residential buildings outside the scope of BS 9251<ref name="No5"></ref>, the requirements of BS EN 12845<ref name="No6">BS EN 12845:2015+A1:2019 Fixed fire-fighting systems. Automatic sprinkler systems. Design, installation and maintenance. BSI</ref> should be followed.
  
==Trade-offs for sprinkler use==
+
==Concessions for sprinkler use==
Trade-offs in terms of fire precautions when life safety sprinkler systems are installed in new buildings can take a variety of forms. Most commonly they can be used to justify some reductions in [[Structural_fire_resistance_requirements|fire ratings]] for the building and also modifications to escape travel distances, number of fire escapes etc. This section describes trade-offs that are available in the four most common documents which are used to design fire precautions in buildings in the UK. These do not include trade-offs that might be developed as part of a [[Structural_fire_engineering| fire engineered]] solution for a building.
+
Concessions in terms of fire precautions when life safety sprinkler systems are installed in new buildings can take a variety of forms. Most commonly sprinkler installation can be used to justify reductions in [[Structural_fire_resistance_requirements|periods of fire resistance]] for the building, modifications to escape travel distances and number of fire escapes. This section describes concessions that are available in the four most common documents which prescribe design fire precautions in buildings in the UK. These regulatory concessions do not include solutions that might be developed as part of a [[Structural_fire_engineering| fire engineered]] solution for a building.
 
   
 
   
===Trade-offs in [[Structural_fire_resistance_requirements#Approved_Document_B|Approved Document B]]<ref name="No1"></ref>===
+
===Concessions in [[Structural_fire_resistance_requirements#Approved_Document_B|Approved Document B]]===
 
{{#image_template:image=File:Table_B4.jpg|caption=[[Structural_fire_resistance_requirements#Approved_Document_B|Approved Document B]]<ref name="No1"></ref> allows a 30 minute reduction in [[Structural_fire_resistance_requirements#Approved_Document_B|fire resistance requirements]] for most buildings under 30 metres in height when life safety sprinkler systems are installed|align=right|wrap=true|width=500}}
 
{{#image_template:image=File:Table_B4.jpg|caption=[[Structural_fire_resistance_requirements#Approved_Document_B|Approved Document B]]<ref name="No1"></ref> allows a 30 minute reduction in [[Structural_fire_resistance_requirements#Approved_Document_B|fire resistance requirements]] for most buildings under 30 metres in height when life safety sprinkler systems are installed|align=right|wrap=true|width=500}}
  
The following is a list of the trade-offs that may be invoked where an appropriate life safety sprinkler system is installed:
+
The following is a list of the concessions that may be invoked where an appropriate life safety sprinkler system is installed:
*In residential homes, fire doors need not be self closing and changes may be made to the occupancies of safe areas (Section 2.46)
+
*In residential homes, fire doors need not be self-closing and changes may be made to the occupancies of safe areas (Section 2.46)
 
*Restrictions on the area allowed for raised storage are removed (Section 7.7)
 
*Restrictions on the area allowed for raised storage are removed (Section 7.7)
*Allowable maximum dimensions of a compartment in a building are increased (Table 8.1)
+
*Allowable maximum dimensions of a compartment in a building are increased (Table 8.1)
*A building in a [[Single_storey_buildings_in_fire_boundary_conditions|boundary condition]] does not need to be designed for base fixity (Section 13.16)
+
*A building in a [[Single_storey_buildings_in_fire_boundary_conditions|boundary condition]] does not need to be designed for base fixity (Section 13.15)
*Where a buildings is in a [[Single_storey_buildings_in_fire_boundary_conditions#Space-separation_in_boundary_conditions|boundary condition]], the boundary distance ''...can be halved, to a minimum distance of 1m. Alternatively, the amount of unprotected area can be doubled'' (Section 13.22).   
+
*Where a buildings is in a [[Single_storey_buildings_in_fire_boundary_conditions#Space-separation_in_boundary_conditions|boundary condition]], the boundary distance ''...can be halved, to a minimum distance of 1m. Alternatively, the amount of unprotected area can be doubled'' (Section 13.21).   
*For buildings requiring fire fighting shafts, the number can be reduced in certain circumstances (Section 17)  
+
*For buildings requiring fire fighting shafts, the number can be reduced in certain circumstances (Section 17.8)  
 
*Mechanical extraction may be used instead of natural ventilation in basements (Section 18.11)
 
*Mechanical extraction may be used instead of natural ventilation in basements (Section 18.11)
 
<br>
 
<br>
 
The specific provisions for [[Structural_fire_resistance_requirements|fire resistance]] for most fire resisting elements, including the structural frame, can be reduced by 30 minutes in many buildings under 30 metres in height (Tables B3, B4).
 
The specific provisions for [[Structural_fire_resistance_requirements|fire resistance]] for most fire resisting elements, including the structural frame, can be reduced by 30 minutes in many buildings under 30 metres in height (Tables B3, B4).
  
===Trade-offs in [[Structural_fire_resistance_requirements#Technical_Handbook_2|Technical Handbook 2]]<ref name="No2"></ref>===
+
===Concessions in [[Structural_fire_resistance_requirements#Technical_Handbook_2022|Technical Handbook 2022]]===
Life safety sprinklers are not mandatory in most buildings in Scotland, with the following exceptions:  enclosed shopping centres; residential care buildings; high rise domestic buildings; sheltered housing complexes and school buildings.
+
Life safety sprinklers are not mandatory in most buildings in Scotland, with the following exceptions:  enclosed shopping centres; residential care buildings; sheltered housing complexes; school buildings; a building containing flats or maisonettes; social housing and shared multi-occupancy residential buildings.
  
Allowable compartment or storey floor areas can be doubled in most buildings if an automatic fire suppression system conforming to the LPC Rules for Automatic Sprinkler Installations<ref name="No7"> LPC Rules for Automatic Sprinkler Installations 2015, incorporating BS EN 12845. Fire Protection Association</ref> are followed. This has the effect of reducing [[Structural_fire_resistance_requirements|fire resistance periods]] in many instances. For example, an office with a floor area of 3000m&sup2; and less than 7.5 metres in height will normally require a medium (60 minutes) period of [[Structural_fire_resistance_requirements#Technical_Handbok_2|fire resistance]]. If a sprinkler system is installed to the specification given in the handbook, this can reduce to short (30 minutes).
+
Allowable compartment or storey floor areas can be doubled in most buildings if an automatic fire suppression system conforming to the LPC Rules for Automatic Sprinkler Installations<ref name="No7"> LPC Rules for Automatic Sprinkler Installations 2015, incorporating BS EN 12845. Fire Protection Association</ref> are followed. As fire resistance periods increase with larger floor areas, the introduction of automatic fire suppression systems and the doubling of limiting floor areas may mean that a lower period of fire resistance is required.  
  
 
[[#Resources|SCI P313]] makes the following statement on design for base fixity for single storey buildings in fire [[Single_storey_buildings_in_fire_boundary_conditions|boundary conditions]]: ''In Scotland, relaxations on boundary conditions are permitted if the building is fitted with a sprinkler system....The Technical Handbook does not state explicitly that fitting sprinklers removes the need to design the column foundations to resist overturning....it is up to the local authorities to grant relaxations to the regulations on an individual basis''.
 
[[#Resources|SCI P313]] makes the following statement on design for base fixity for single storey buildings in fire [[Single_storey_buildings_in_fire_boundary_conditions|boundary conditions]]: ''In Scotland, relaxations on boundary conditions are permitted if the building is fitted with a sprinkler system....The Technical Handbook does not state explicitly that fitting sprinklers removes the need to design the column foundations to resist overturning....it is up to the local authorities to grant relaxations to the regulations on an individual basis''.
  
===Trade-offs in [[Structural_fire_resistance_requirements#Technical_Booklet_E|Technical Booklet E]]<ref name="No3"></ref>===
+
===Concessions in [[Structural_fire_resistance_requirements#Technical_Booklet_E|Technical Booklet E]]===
Trade-offs are broadly similar to those in [[Structural_fire_resistance_requirements#Approved_Document_B|Approved Document B]]<ref name="No1"></ref>:
+
Concessions are broadly similar to those in [[Structural_fire_resistance_requirements#Approved_Document_B|Approved Document B]]<ref name="No1"></ref>:
 
*The specific provisions for [[Structural_fire_resistance_requirements|fire resistance]] for most fire resisting elements, including the structural frame, can be reduced by 30 minutes in many buildings under 30 metres in height (Tables 4.1, 4.2)
 
*The specific provisions for [[Structural_fire_resistance_requirements|fire resistance]] for most fire resisting elements, including the structural frame, can be reduced by 30 minutes in many buildings under 30 metres in height (Tables 4.1, 4.2)
 
*Restrictions on the area allowed for raised storage are removed (Section 4.14)
 
*Restrictions on the area allowed for raised storage are removed (Section 4.14)
Line 46: Line 46:
 
<br>
 
<br>
  
===Trade-offs in [[Structural_fire_resistance_requirements#BS_9999|BS 9999]]<ref name="No4"></ref>===
+
===Concessions in [[Structural_fire_resistance_requirements#BS_9999|BS 9999]]===
[[Structural_fire_resistance_requirements#BS_9999|BS 9999]]<ref name="No4"></ref> generally allows more attractive trade-offs for automatic sprinkler installation and automatic fire detection than are generally available in [[Structural_fire_resistance_requirements#Approved_Document_B|Approved Document B]]<ref name="No1"></ref> or [[Structural_fire_resistance_requirements#Technical_Booklet_E|Technical Booklet E]]<ref name="No3"></ref>. The following example is given for a shop with a risk profile requiring 45 minutes fire resistance, a maximum two way travel distance of 40 metres, a ceiling height of 4.5 metres and a minimum door width per person of 6mm.
+
[[Structural_fire_resistance_requirements#BS_9999|BS 9999]]<ref name="No4"></ref> generally allows more attractive concessions for automatic sprinkler installation and automatic fire detection than are generally available in [[Structural_fire_resistance_requirements#Approved_Document_B|Approved Document B]]<ref name="No1"></ref> or [[Structural_fire_resistance_requirements#Technical_Booklet_E|Technical Booklet E]]<ref name="No3"></ref>. The provision of an automatic fire suppression system permits a reduction in fire growth rate, allowing longer travel distances, smaller doors, larger compartments and reduced fire resistance periods.
 
 
''If a shop sales area with this risk profile is fitted with sprinklers, its risk profile reduces and the fire rating can be reduced from 45 to 30 minutes. The maximum two-way travel distance is increased from 40 metres to 50 metres. Similarly the maximum one-way travel distance may be increased from 16 metres to 20 metres. The minimum door width per person can be reduced to 4.1 mm.''
 
  
 
==References==
 
==References==

Latest revision as of 14:02, 11 July 2022

All the major Government published documents describing methods of designing buildings to safeguard life in buildings in the event of fire: Approved Document B[1]; Scottish Technical Handbook 2022[2] and Technical Booklet E[3] in Northern Ireland allow the use of life safety sprinklers in buildings. In some instances, the use of life safety sprinklers is mandatory. BS 9999[4] also makes provision for their use. Note that, since 2014, a separate version of Approved Document B has existed for Wales.

Where sprinklers operate on the exploding bulb principle, the sprinkler head activates when the fluid expands under the effects of rising temperatures and breaks the glass. Only the sprinklers in the vicinity of the fire are activated. Around 60% of fires are supressed by the activation of no more than four sprinkler heads. Further information on the operating principles for automatic sprinklers and their efficiency at controlling and extinguishing fires can be found at the British Automatic Fire Sprinkler Association website.

[top]Sprinklers in UK fire codes and standards

The emphasis placed on the use of sprinklers in buildings in fire codes and standards varies between Approved Document B[1]; Scottish Technical Handbook 2022 [2], Technical Booklet E[3] and BS 9999[4].

For dwellings and residential buildings, guidance on the installation of life safety sprinklers is given in BS 9251[5]. For non-residential buildings or dwellings and residential buildings outside the scope of BS 9251[5], the requirements of BS EN 12845[6] should be followed.

[top]Concessions for sprinkler use

Concessions in terms of fire precautions when life safety sprinkler systems are installed in new buildings can take a variety of forms. Most commonly sprinkler installation can be used to justify reductions in periods of fire resistance for the building, modifications to escape travel distances and number of fire escapes. This section describes concessions that are available in the four most common documents which prescribe design fire precautions in buildings in the UK. These regulatory concessions do not include solutions that might be developed as part of a fire engineered solution for a building.

[top]Concessions in Approved Document B

               Table B4.jpg
Approved Document B[1] allows a 30 minute reduction in fire resistance requirements for most buildings under 30 metres in height when life safety sprinkler systems are installed

The following is a list of the concessions that may be invoked where an appropriate life safety sprinkler system is installed:

  • In residential homes, fire doors need not be self-closing and changes may be made to the occupancies of safe areas (Section 2.46)
  • Restrictions on the area allowed for raised storage are removed (Section 7.7)
  • Allowable maximum dimensions of a compartment in a building are increased (Table 8.1)
  • A building in a boundary condition does not need to be designed for base fixity (Section 13.15)
  • Where a buildings is in a boundary condition, the boundary distance ...can be halved, to a minimum distance of 1m. Alternatively, the amount of unprotected area can be doubled (Section 13.21).
  • For buildings requiring fire fighting shafts, the number can be reduced in certain circumstances (Section 17.8)
  • Mechanical extraction may be used instead of natural ventilation in basements (Section 18.11)


The specific provisions for fire resistance for most fire resisting elements, including the structural frame, can be reduced by 30 minutes in many buildings under 30 metres in height (Tables B3, B4).

[top]Concessions in Technical Handbook 2022

Life safety sprinklers are not mandatory in most buildings in Scotland, with the following exceptions: enclosed shopping centres; residential care buildings; sheltered housing complexes; school buildings; a building containing flats or maisonettes; social housing and shared multi-occupancy residential buildings.

Allowable compartment or storey floor areas can be doubled in most buildings if an automatic fire suppression system conforming to the LPC Rules for Automatic Sprinkler Installations[7] are followed. As fire resistance periods increase with larger floor areas, the introduction of automatic fire suppression systems and the doubling of limiting floor areas may mean that a lower period of fire resistance is required.

SCI P313 makes the following statement on design for base fixity for single storey buildings in fire boundary conditions: In Scotland, relaxations on boundary conditions are permitted if the building is fitted with a sprinkler system....The Technical Handbook does not state explicitly that fitting sprinklers removes the need to design the column foundations to resist overturning....it is up to the local authorities to grant relaxations to the regulations on an individual basis.

[top]Concessions in Technical Booklet E

Concessions are broadly similar to those in Approved Document B[1]:

  • The specific provisions for fire resistance for most fire resisting elements, including the structural frame, can be reduced by 30 minutes in many buildings under 30 metres in height (Tables 4.1, 4.2)
  • Restrictions on the area allowed for raised storage are removed (Section 4.14)
  • Allowable maximum floor areas of a compartment in a building are increased (Table 4.4)
  • Where a buildings is in a boundary condition, the thermal radiation intensities ....and the distances .....may be halved subject to there being a minimum distance of 1 m. Alternatively, the amount of unprotected area may be doubled if the calculated boundary distance is maintained (Section 5.13)
  • For buildings requiring fire fighting shafts, the number can be reduced in certain circumstances (Section 6.4)
  • Mechanical extraction may be used instead of natural ventilation in basements (Section 6.16)


[top]Concessions in BS 9999

BS 9999[4] generally allows more attractive concessions for automatic sprinkler installation and automatic fire detection than are generally available in Approved Document B[1] or Technical Booklet E[3]. The provision of an automatic fire suppression system permits a reduction in fire growth rate, allowing longer travel distances, smaller doors, larger compartments and reduced fire resistance periods.

[top]References

  1. 1.0 1.1 1.2 1.3 1.4 Approved Document B (Fire safety, Volume 2 – Buildings other than Dwellings), 2019 edition incorporating 2020 amendments – for use in England . Ministry of Housing, Communities & Local Government
  2. 2.0 2.1 Building standards technical handbook: 2022 – Non-domestic, Section 2 – Fire, The Scottish Government
  3. 3.0 3.1 3.2 Technical Booklet E, Fire safety, Building Regulations (Northern Ireland) 2012, Department of Finance and Personnel of the Northern Ireland Government, 2012
  4. 4.0 4.1 4.2 BS 9999: 2017, Fire safety in the design, management and use of buildings - Code of practice. BSI
  5. 5.0 5.1 BS 9251:2021 Sprinkler systems for residential and domestic occupancies – Code of practice. BSI
  6. BS EN 12845:2015+A1:2019 Fixed fire-fighting systems. Automatic sprinkler systems. Design, installation and maintenance. BSI
  7. LPC Rules for Automatic Sprinkler Installations 2015, incorporating BS EN 12845. Fire Protection Association