Passive fire protection materials insulate steel structures from the effects of the high temperatures that may be generated in fire. They can be divided into two types, non-reactive, of which the most common types are [[Fire_protecting_structural_steelwork#Boards|boards]] and [[Fire_protecting_structural_steelwork#Sprays|sprays]], and reactive, of which [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] are the most common example. [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|Thin film intumescent coatings]]  can be either on-site or [[Fire_protecting_structural_steelwork#Off_site_applied_intumescent_coatings|off-site applied]].  
 
Passive fire protection materials insulate steel structures from the effects of the high temperatures that may be generated in fire. They can be divided into two types, non-reactive, of which the most common types are [[Fire_protecting_structural_steelwork#Boards|boards]] and [[Fire_protecting_structural_steelwork#Sprays|sprays]], and reactive, of which [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] are the most common example. [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|Thin film intumescent coatings]]  can be either on-site or [[Fire_protecting_structural_steelwork#Off_site_applied_intumescent_coatings|off-site applied]].  
 
The UK is fortunate in having an efficient and competitive structural fire protection industry which delivers excellent quality at low cost.
 
 
{{#image_template:image=File:Intumescent_coating_example_3.png|caption= [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|Thin film intumescent coatings]] <br>''(Image courtesy of Sherwin-Williams Protective and Marine Coatings)''|align=right|wrap=true|width=400}}
 
{{#image_template:image=File:Intumescent_coating_example_3.png|caption= [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|Thin film intumescent coatings]] <br>''(Image courtesy of Sherwin-Williams Protective and Marine Coatings)''|align=right|wrap=true|width=400}}
  
 
==Intumescent Coatings==
 
==Intumescent Coatings==
 
{{#image_template:image=File:Intumescent_coating_expanded.png|caption=Expanded [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coating]]|align=right|wrap=true|width=250}}
 
{{#image_template:image=File:Intumescent_coating_expanded.png|caption=Expanded [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coating]]|align=right|wrap=true|width=250}}
Intumescent coatings are paint like materials which are inert at low temperatures but which provide insulation as a result of a complex chemical reaction at temperatures typically of about 200-250°C. At these temperatures the properties of steel will not be affected. As a result of this reaction they swell and provide an expanded layer of low conductivity char.  
+
Intumescent coatings are paint-like materials which are inert at low temperatures but which provide insulation as a result of a complex chemical reaction at temperatures typically of about 200-250°C. At these temperatures the properties of steel will not be affected. As a result of this reaction the coatings swell and provide an expanded layer of low conductivity char.  
  
Intumescent coatings can be divided into two broad families: [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film]] and [[Fire_protecting_structural_steelwork#Thick_film_intumescent_coatings|thick film]]. [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|Thin film]] materials are either solvent based or water based and are mainly used for building fires. [[Fire_protecting_structural_steelwork#Thick_film_intumescent_coatings|Thick film intumescent coatings]] were originally developed for the off-shore and hydrocarbon industries but have been modified for use in buildings.
+
Intumescent coatings can be divided into two broad families: [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film]] and [[Fire_protecting_structural_steelwork#Thick_film_intumescent_coatings|thick film]]. [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|Thin film]] materials are either solvent-based or water-based and are mainly used to protect building structures. [[Fire_protecting_structural_steelwork#Thick_film_intumescent_coatings|Thick film intumescent coatings]] were originally developed for the off-shore and hydrocarbon industries but have been modified for use in buildings.
  
 
===Thin film intumescent coatings===
 
===Thin film intumescent coatings===
 
Thin film intumescent coating systems generally have three components, a primer, a basecoat (the part which reacts in the fire) and a sealer coat. The basecoat usually comprises the following ingredients:  
 
Thin film intumescent coating systems generally have three components, a primer, a basecoat (the part which reacts in the fire) and a sealer coat. The basecoat usually comprises the following ingredients:  
 
*A catalyst which decomposes to produce a mineral acid such as phosphoric acid.  
 
*A catalyst which decomposes to produce a mineral acid such as phosphoric acid.  
*A carbonific such as starch which combines with the mineral acid to form a carbonaceous char.  
+
*A carbonific such as starch which combines with the mineral acid to form a large volume of carbonaceous char.  
 
*A binder or resin which softens at a predetermined temperature.  
 
*A binder or resin which softens at a predetermined temperature.  
 
*A spumific agent which decomposes together with the melting of the binder, to liberate large volumes of non-flammable gases. These gases include carbon dioxide, ammonia and water vapour. The production of these gases causes the carbonaceous char to swell or foam and expand to provide an insulating layer many times the original coating thickness.  
 
*A spumific agent which decomposes together with the melting of the binder, to liberate large volumes of non-flammable gases. These gases include carbon dioxide, ammonia and water vapour. The production of these gases causes the carbonaceous char to swell or foam and expand to provide an insulating layer many times the original coating thickness.  
 
<br>
 
<br>
They are mainly used in buildings where the [[Structural_fire_resistance_requirements|fire resistance requirements]] are 30, 60 and 90 minutes. In recent years, a number of products have been developed which can provide 120 minutes [[Structural_fire_resistance_requirements|fire resistance ]]. They can be applied either on-site or [[Fire_protecting_structural_steelwork#Off_site_applied_intumescent_coatings|off-site]].  
+
Thin film intumescent coatings are mainly used in buildings where the [[Structural_fire_resistance_requirements|fire resistance requirements]] are 30, 60 and 90 minutes. In recent years, a number of products have been developed which can provide 120 minutes [[Structural_fire_resistance_requirements|fire resistance ]]. They can be applied either on-site or [[Fire_protecting_structural_steelwork#Off_site_applied_intumescent_coatings|off-site]].  
In general, most on-site application is carried out using water based materials. However, where the structure to which the material is applied is not to have an end use in a dry, heated [[Corrosion_protection#Corrosion_of_structural_steel|(C1)]] environment, solvent based materials are commonly used. Solvent based materials also tend to be able to cover a wider range of [[Calculating_section_factors|section factors]] than water based materials and can be used on-site to protect smaller sections requiring high thicknesses.  
+
In general, for structures in a C1 environment (dry internal steelwork), most on-site application is carried out using water-based materials. For more aggressive environments, solvent-based products are commonly applied. Solvent-based materials also tend to be able to cover a wider range of [[Calculating_section_factors|section factors]] than water-based materials and can be used on-site to protect smaller sections requiring high thicknesses.  
  
Both solvent based and water based coatings can be used to achieve [[Hollow_sections_in_fire#Aesthetic_finishes_using_thin_film_intumescent_coatings|attractive surface finishes]].  If a decorative or bespoke finish is required, this should be included in the specification. Thin film intumescents have the added advantages that they can easily cover complex shapes and post-protection service installation is relatively simple.
+
Both solvent-based and water-based coatings can be used to achieve [[Hollow_sections_in_fire#Aesthetic_finishes_using_thin_film_intumescent_coatings|attractive surface finishes]].  If a decorative or bespoke finish is required, this should be included in the specification. Thin film intumescents have the added advantages that they can easily cover complex shapes and post-protection service installation is relatively simple.
  
Typical expansion ratios are about 50:1, i.e. a 1mm thick coating will expand to about 50mm when affected by fire.
+
Typical expansion ratios are about 50:1, i.e. a 1mm thick coating will expand to about 50mm when affected by heat.
  
 
Detailed guidance on the specification and installation of site applied, thin film intumescent coatings is available from the Association for Specialist Fire Protection<ref name="No1">ASFP Technical Guidance Document - TGD 11. Code of practice for the specification & on-site installation of intumescent coatings for fire protection of structural steelwork</ref>.
 
Detailed guidance on the specification and installation of site applied, thin film intumescent coatings is available from the Association for Specialist Fire Protection<ref name="No1">ASFP Technical Guidance Document - TGD 11. Code of practice for the specification & on-site installation of intumescent coatings for fire protection of structural steelwork</ref>.
Line 32: Line 30:
 
<br>
 
<br>
  
===Off site applied intumescent coatings===
+
===Off-site applied intumescent coatings===
 
{{#image_template:image=File:Off_site_application.png|align=right|caption=Off-site application|wrap=true|width=300}}
 
{{#image_template:image=File:Off_site_application.png|align=right|caption=Off-site application|wrap=true|width=300}}
The development of an industry to apply [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] off-site has been a UK success story which is now being exported across the world. The process usually involves application in a large, well ventilated and heated facility remote from the construction site. It has a number of distinct advantages:  
+
Off-site application usually involves coating the steelwork in a large, well ventilated and heated facility remote from the construction site. Off-site application has a number of distinct advantages:  
*Quicker construction
+
*Reduced site programme
 
*Improved quality control
 
*Improved quality control
 
*Reduction  in site disruption
 
*Reduction  in site disruption
Line 42: Line 40:
 
*Easier servicing installation
 
*Easier servicing installation
 
<br>
 
<br>
Specifiers should be aware that off-site applied [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] are used mainly for non-aesthetic end uses. Aesthetic finishes are possible, and have been achieved, using off-site application but it requires an additional level of care and attention. This is because some damage in transit is inevitable, even though applicators work to minimise it. It is difficult (but not of course impossible) to repair damage to match the appearance of the rest of the coating but this adds a layer of complexity to the work.   
+
Specifiers should be aware that off-site applied [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] are used mainly for non-aesthetic end uses. Aesthetic finishes are possible, and have been achieved using off-site application but require increased care, particularly when handling the steelwork. Some damage in transit is inevitable, which will need to be repaired; producing a perfect match is difficult.   
  
 
Applying [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] off-site is a specialised task. The Association for Specialist Fire Protection publishes a guidance document<ref name="No2">ASFP Technical Guidance Document - TGD 16. Code of Practice for Off-site Applied Thin Film Intumescent Coatings</ref> to assist specifiers. This includes a model specification from which clauses can be taken to put in the specifier’s own contract documents.   
 
Applying [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] off-site is a specialised task. The Association for Specialist Fire Protection publishes a guidance document<ref name="No2">ASFP Technical Guidance Document - TGD 16. Code of Practice for Off-site Applied Thin Film Intumescent Coatings</ref> to assist specifiers. This includes a model specification from which clauses can be taken to put in the specifier’s own contract documents.   
  
Off-site application is more expensive than its on-site equivalent in terms of up-front costs but the value of the advantages can make it more cost effective overall. This is widely recognised and [[Fire_protecting_structural_steelwork#Trends_in_structural_fire_protection|market surveys]] show that this process has a significant market share in the UK.
+
Off-site application is more expensive than its on-site equivalent in terms of up-front costs but the advantages can make it more cost-effective overall. Off-site application has a significant market share in the UK.
 
<gallery caption="Application of thin film intumescent coatings offsite" perrow=2 widths=300px heights=250px>  
 
<gallery caption="Application of thin film intumescent coatings offsite" perrow=2 widths=300px heights=250px>  
 
Image:Off_site_application_2.png
 
Image:Off_site_application_2.png
Line 58: Line 56:
 
Image:THick_film_intumescent.png|Preformed casings using thick film epoxy intumescent<br>''(Image courtesy of Nuvia)''</gallery>
 
Image:THick_film_intumescent.png|Preformed casings using thick film epoxy intumescent<br>''(Image courtesy of Nuvia)''</gallery>
 
Thick film intumescent coatings are usually epoxy based and typically have a much higher dry film thickness than [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film ]] alternatives. These materials are tough and durable and were originally developed for use with [[Fire_testing#Other_standard_fire_tests|hydrocarbon fires]], where the test heating regime is much more severe than that used for most industrial and commercial applications.
 
Thick film intumescent coatings are usually epoxy based and typically have a much higher dry film thickness than [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film ]] alternatives. These materials are tough and durable and were originally developed for use with [[Fire_testing#Other_standard_fire_tests|hydrocarbon fires]], where the test heating regime is much more severe than that used for most industrial and commercial applications.
A number of manufacturers have modified their materials for use in [[Fire_testing|cellulosic fires]]. These modified materials are usually used in situations where the benefits of [[Fire_protecting_structural_steelwork#Intumescent_coatings|intumescent coatings]] in terms of appearance, weight and thickness are required but where circumstances are too severe, or maintenance too difficult, to allow the use of [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film materials]]. Typical recent examples have occurred in external steel in high rise buildings and exposed marine environments.
+
A number of manufacturers have modified their materials for use in [[Fire_testing|cellulosic fires]]. These modified materials are usually used in situations where the benefits of [[Fire_protecting_structural_steelwork#Intumescent_coatings|intumescent coatings]] in terms of appearance, weight and thickness are required but where circumstances are too severe, or maintenance too difficult, to allow the use of [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film materials]]. Typical examples where thick film coatings may be appropriate include external steel in high rise buildings and exposed marine environments.
 
   
 
   
 
Expansion ratios for thick film intumescents are much lower than for [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film materials]], typically about 5:1. Aesthetic finishes are possible and it can also be supplied in the form of preformed casings.  
 
Expansion ratios for thick film intumescents are much lower than for [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film materials]], typically about 5:1. Aesthetic finishes are possible and it can also be supplied in the form of preformed casings.  
Line 65: Line 63:
 
==Boards==
 
==Boards==
 
{{#image_template:image=File:Board_and_intumescent.png|caption=Interfacing between boards and [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] is quite common<br>''(Image courtesy of Promat Ltd.)''|align=right|wrap=true|width=200}}
 
{{#image_template:image=File:Board_and_intumescent.png|caption=Interfacing between boards and [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] is quite common<br>''(Image courtesy of Promat Ltd.)''|align=right|wrap=true|width=200}}
Boards are widely used for structural fire protection in the UK. They are used both where the protection system is in full view and where it is hidden. They offer the specifier a clean, boxed appearance and have the additional advantages that application is a dry trade and may not have significant impacts on other activities. Also, boards are factory manufactured and thicknesses can be guaranteed. Furthermore, boards can be applied on unpainted steelwork.
+
Boards are widely used for structural fire protection in the UK. They are used both where the protection system is in full view and where it is hidden. They offer the specifier a clean, boxed appearance and have the additional advantages that application is a dry trade and generally have minimal impacts on other activities. Fire protection boards are factory manufactured and have consistent thickness. Board protection can be applied to unpainted steelwork.
  
There are broadly two families of board protection, lightweight and heavyweight. Lightweight boards are typically 150-250kg/m&sup3; and are not usually suitable for decorative finishes. They are typically used where aesthetics are not important and are cheaper than heavyweight equivalents.  
+
There are broadly two families of board protection, lightweight and heavyweight. Lightweight boards are typically 150-250kg/m&sup3; and are not usually suitable for decorative finishes. They are typically used where an aesthetic finish is not required and are cheaper than heavyweight equivalents.  
Heavyweight boards are usually in the range 700-950kg/m&sup3; and will generally accept decorative finishes. They are typically used where aesthetics are important.  
+
Heavyweight boards are usually in the range 700-950kg/m&sup3; and will generally accept decorative finishes. They are typically used where an aesthetic finish is required.  
  
 
Both types of board may be used in limited external conditions but the advice of the manufacturer should be sought.  
 
Both types of board may be used in limited external conditions but the advice of the manufacturer should be sought.  
Line 80: Line 78:
 
==Sprays==
 
==Sprays==
 
{{#image_template:image=File:Cementitious_spray_on_beams_with_openings.jpg|caption= Cementitious spray on beams<br>''(Image courtesy of Promat Ltd.)'' |align=right|wrap=true|width=300}}
 
{{#image_template:image=File:Cementitious_spray_on_beams_with_openings.jpg|caption= Cementitious spray on beams<br>''(Image courtesy of Promat Ltd.)'' |align=right|wrap=true|width=300}}
Spray protection is extensively used in the United States but is less common in the United Kingdom. It has the advantage that it can be used to cover complex shapes and details and also that costs do not increase significantly with increases in protection thickness. This is because much of the cost of application is in the labour and equipment and a minority is in the cost of the material. Some materials can also be used in [[Fire_and_steel_construction#External_steelwork_in_fire|external]] and [[Fire_testing#Other_standard_fire_tests|hydrocarbon fire]] applications.  
+
Spray protection is extensively used in the United States but is less common in the United Kingdom. It has the advantage that it can be used to cover complex shapes and details and also that costs do not increase significantly with increases in protection thickness. This is because much of the cost of application is in the labour and equipment rather than the cost of the material. Some materials can also be used in [[Fire_and_steel_construction#External_steelwork_in_fire|external]] and [[Fire_testing#Other_standard_fire_tests|hydrocarbon fire]] applications.  
  
Sprays are not suitable for aesthetic purposes. Also, application is a wet trade and this may have impacts on other site operations. Allowance may have to be made in costing for the possible requirement for prevention of overspray. Detailed guidance on the installation of spray protection systems is available from the Association for Specialist Fire Protection<ref name="No4">ASFP Technical Guidance Document - TGD 15. Code of practice for the installation & inspection of sprayed non-reactive coatings for the fire protection of structural steelwork</ref>.
+
Sprays are not suitable when an aesthetic finish is required. Spray application is a wet trade which is likely to have a significant effect on site operations. Overspray is is to be expected, which requires protection of other building elements (and may require complete encapsulation at the edges of the building). Cleaning floors after spray operations is also required. Detailed guidance on the installation of spray protection systems is available from the Association for Specialist Fire Protection<ref name="No4">ASFP Technical Guidance Document - TGD 15. Code of practice for the installation & inspection of sprayed non-reactive coatings for the fire protection of structural steelwork</ref>.
  
 
==Flexible blanket systems==
 
==Flexible blanket systems==
Line 91: Line 89:
 
==Concrete encasement==
 
==Concrete encasement==
 
{{#image_template:image=File:Concrete_encasement.png|caption=Concrete encasement of structural steelwork|align=right|wrap=true|width=300}}
 
{{#image_template:image=File:Concrete_encasement.png|caption=Concrete encasement of structural steelwork|align=right|wrap=true|width=300}}
Until the late 1970s, concrete was by far the most common form of fire protection for structural steelwork.  However the introduction of lightweight, proprietary systems such as [[Fire_protecting_structural_steelwork#Boards|boards]], [[Fire_protecting_structural_steelwork#Sprays|sprays]] and [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] has seen a dramatic reduction in its use. Nevertheless, concrete encasement has its place and it continues to have a small percentage of the fire protection market with other traditional methods such as blockwork encasement also used occasionally.
+
Until the late 1970s, concrete was by far the most common form of fire protection for structural steelwork.  However the introduction of lightweight, proprietary systems such as [[Fire_protecting_structural_steelwork#Boards|boards]], [[Fire_protecting_structural_steelwork#Sprays|sprays]] and [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] has seen a dramatic reduction in its use. Nevertheless, concrete encasement has its place and it continues to have a small percentage of the fire protection market with other traditional methods such as blockwork encasement.
 
The principal advantage of concrete is durability. It tends to be used where resistance to impact damage, abrasion and weather exposure are important e.g. warehouses, underground car parks and external structures.
 
The principal advantage of concrete is durability. It tends to be used where resistance to impact damage, abrasion and weather exposure are important e.g. warehouses, underground car parks and external structures.
 
The principal disadvantages are:  
 
The principal disadvantages are:  
Line 101: Line 99:
  
 
==Partial protection==
 
==Partial protection==
[[Fire_testing#The_standard_fire_test|Standard fire tests]] have shown that structural members which are designed to not be fully exposed to fire can exhibit substantial levels of [[Structural_fire_resistance_requirements|fire resistance]] without applied protection. Methods have been developed using this effect to achieve [[Structural_fire_resistance_requirements|30 and 60 minutes fire resistance]]. Where higher [[Structural_fire_resistance_requirements|periods of fire resistance]] are called for, reduced fire protection thicknesses can be applied to the exposed steelwork since the heated perimeter, and therefore the [[Calculating_section_factors|section factor]], is less than that for the fully exposed case. See [[Calculating_section_factors#Calculation_of_section_factors_for_partially_exposed_sections|here]] for more details.
+
[[Fire_testing#The_standard_fire_test|Standard fire tests]] have shown that structural members which are only partially exposed to fire can exhibit substantial levels of [[Structural_fire_resistance_requirements|fire resistance]] without applied protection. Methods have been developed to demonstrate [[Structural_fire_resistance_requirements|30 and 60 minutes fire resistance]]. Where higher [[Structural_fire_resistance_requirements|periods of fire resistance]] are called for, reduced fire protection thicknesses can be applied to the remaining exposed steelwork since the heated perimeter, and therefore the [[Calculating_section_factors|section factor]]  is less than that for the fully exposed case. See [[Calculating_section_factors#Calculation_of_section_factors_for_partially_exposed_sections|here]] for more details.
  
 
There are five ways in which partial protection can be used:
 
There are five ways in which partial protection can be used:
  
===Block infilled columns===
+
===Block-infilled columns===
 
30 minutes [[Structural_fire_resistance_requirements|fire resistance]] can be achieved by the use of autoclaved, aerated concrete blocks cemented between the flanges and tied to the web of [[Steel_construction_products#Standard_open_sections|rolled sections]]. Longer [[Structural_fire_resistance_requirements|fire resistance periods]] are possible by protecting only the exposed flanges. Guidance is available from the Building Research Establishment<ref name="No7">BRE Digest 317. Fire resistant steel structures: free-standing blockwork-filled columns and stanchions. Building Research Establishment</ref>.
 
30 minutes [[Structural_fire_resistance_requirements|fire resistance]] can be achieved by the use of autoclaved, aerated concrete blocks cemented between the flanges and tied to the web of [[Steel_construction_products#Standard_open_sections|rolled sections]]. Longer [[Structural_fire_resistance_requirements|fire resistance periods]] are possible by protecting only the exposed flanges. Guidance is available from the Building Research Establishment<ref name="No7">BRE Digest 317. Fire resistant steel structures: free-standing blockwork-filled columns and stanchions. Building Research Establishment</ref>.
<gallery caption="Block filled [[Steel_construction_products#Standard_open_sections|columns]]" perrow=2 widths=250px heights=500px>  
+
<gallery caption="Block-infilled [[Steel_construction_products#Standard_open_sections|columns]]" perrow=2 widths=250px heights=500px>  
 
Image:Block_filled_column.png|
 
Image:Block_filled_column.png|
 
Image:BRE_Digest_317.png|BRE guidance on block filled [[Steel_construction_products#Standard_open_sections|columns]]
 
Image:BRE_Digest_317.png|BRE guidance on block filled [[Steel_construction_products#Standard_open_sections|columns]]
Line 115: Line 113:
 
===Shelf angle floor beams===
 
===Shelf angle floor beams===
 
{{#image_template:image=File:Shelf_angle_floor_beam.png|align=right|wrap=true|width=200}}
 
{{#image_template:image=File:Shelf_angle_floor_beam.png|align=right|wrap=true|width=200}}
Shelf angle floor beams are [[Steel_construction_products#Standard_open_sections|beams]] with [[Steel_construction_products#Standard_open_sections|angles]] welded or bolted to the web to support the floor slab. This protects the top part of the [[Steel_construction_products#Standard_open_sections|beam]] from the fire while the bottom part remains exposed. Fire resistance increases as the position of the supporting [[Steel_construction_products#Standard_open_sections|angle]] is moved further down the [[Steel_construction_products#Standard_open_sections|beam]] and [[Structural_fire_resistance_requirements|60 minutes fire resistance]] is achievable in some instances. Shelf angle floor beams are more commonly bolted rather than welded as shown in the accompanying photograph.  
+
Shelf angle floor beams are [[Steel_construction_products#Standard_open_sections|beams]] with [[Steel_construction_products#Standard_open_sections|angles]] welded or bolted to the web to support the floor slab. The floor slab protects the top part of the [[Steel_construction_products#Standard_open_sections|beam]] from the fire while the bottom part remains exposed. Fire resistance increases as the position of the supporting [[Steel_construction_products#Standard_open_sections|angle]] is moved further down the [[Steel_construction_products#Standard_open_sections|beam]] and [[Structural_fire_resistance_requirements|60 minutes fire resistance]] is achievable in some instances. Shelf angle floor beams are more commonly bolted rather than welded as shown in the accompanying photograph.  
  
 
Guidance is available in [[#Resources|SCI P126]].
 
Guidance is available in [[#Resources|SCI P126]].
Line 129: Line 127:
  
 
===Web infilled columns===
 
===Web infilled columns===
Sixty minutes [[Structural_fire_resistance_requirements|fire resistance]] can be achieved for [[Steel_construction_products#Standard_open_sections|columns]] when normal weight, poured concrete is fixed between the flanges by shear connectors attached to the web. The concrete is retained by a web stiffener fixed at the bottom of the connection zone.  
+
Sixty minutes [[Structural_fire_resistance_requirements|fire resistance]] can be achieved for [[Steel_construction_products#Standard_open_sections|columns]] when normal weight concrete is cast between the flanges and connected by shear connectors attached to the web. The concrete is retained by a web stiffener fixed at the bottom of the connection zone.  
  
 
The load carrying capacity of the concrete is ignored in the design of the [[Steel_construction_products#Standard_open_sections|columns]] but in fire, as the exposed [[Design_using_structural_fire_standards#Steelwork_strength_in_fire|steel weakens at high temperatures]], the load carried by the flanges is progressively transferred to the concrete. This provides stability  for periods of [[Structural_fire_resistance_requirements|fire resistance up to 60 minutes ]]. The connection zone is [[Fire_protecting_structural_steelwork|fire protected]] along with the beam.  Guidance is available in the Steel Construction Institute publication [[#Resources|SCI P124]].
 
The load carrying capacity of the concrete is ignored in the design of the [[Steel_construction_products#Standard_open_sections|columns]] but in fire, as the exposed [[Design_using_structural_fire_standards#Steelwork_strength_in_fire|steel weakens at high temperatures]], the load carried by the flanges is progressively transferred to the concrete. This provides stability  for periods of [[Structural_fire_resistance_requirements|fire resistance up to 60 minutes ]]. The connection zone is [[Fire_protecting_structural_steelwork|fire protected]] along with the beam.  Guidance is available in the Steel Construction Institute publication [[#Resources|SCI P124]].
Line 140: Line 138:
 
===Composite beams and columns with full and partial concrete encasement===
 
===Composite beams and columns with full and partial concrete encasement===
 
{{#image_template:image=File:Reinforced_column.png|caption=Reinforced column|align=right|wrap=true|width=200}}
 
{{#image_template:image=File:Reinforced_column.png|caption=Reinforced column|align=right|wrap=true|width=200}}
This is a form of construction which has been introduced to the UK by the publication of BS EN 1994-1-2<ref name="No6"></ref>, which describes the systems and also includes tabulated design guidance.  It consists of steel beams and columns in which fire resistance is achieved by the inclusion of reinforcement between the flanges, held in position by concrete. [[Structural_fire_resistance_requirements|Fire resistance periods]] up to 120 minutes is achievable on [[Steel_construction_products#Standard_open_sections|columns]] using this approach and 180 minutes on [[Steel_construction_products#Standard_open_sections|beams]].  
+
This is a form of construction which has been introduced by the publication of BS EN 1994-1-2<ref name="No6"></ref>, which describes the system and also includes tabulated design guidance.  It consists of steel beams and columns in which fire resistance is achieved by the addition of reinforced concrete between the member flanges. [[Structural_fire_resistance_requirements|Fire resistance periods]] up to 120 minutes is achievable on [[Steel_construction_products#Standard_open_sections|columns]] using this approach and 180 minutes on [[Steel_construction_products#Standard_open_sections|beams]].  
Guidance is also given on enhancement to full concrete encasement by the inclusion of rebar and up to 240 minutes  [[Structural_fire_resistance_requirements|fire resistance]] can be achieved. However, this requirement is rare in the UK.
+
Guidance is also given on full concrete encasement and up to 240 minutes  [[Structural_fire_resistance_requirements|fire resistance]] can be achieved.
  
 
==Protecting [[Steel_construction_products#Cellular_beams|cellular beams]]==
 
==Protecting [[Steel_construction_products#Cellular_beams|cellular beams]]==
 
{{#image_template:image=File:Cellular_beam_protected.png|caption=A common scene in UK construction. A [[Steel_construction_products#Cellular_beams|cellular beam]] protected using a [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coating]]|align=right|wrap=true|width=350}}
 
{{#image_template:image=File:Cellular_beam_protected.png|caption=A common scene in UK construction. A [[Steel_construction_products#Cellular_beams|cellular beam]] protected using a [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coating]]|align=right|wrap=true|width=350}}
  
For many years, beams with multiple web openings manufactured by splitting and welding hot rolled [[Steel_construction_products#Standard_open_sections|beams and columns]] (castellated and [[Steel_construction_products#Cellular_beams|cellular beams]]), were fire protected on the basis of the [[Calculating_section_factors|section factor]] of the parent section plus 20%. This was based on the results of a number of tests on castellated beams which showed a small increase in heating rate compared to [[Steel_construction_products#Standard_open_sections|hot rolled sections]]. When a process of manufacturing [[Steel_construction_products#Cellular_beams|cellular beams]] from plates was developed, the 20% rule was retained. The default [[Design_using_structural_fire_standards#Steelwork_strength_in_fire|limiting temperature]] for [[Steel_construction_products#Cellular_beams|cellular beams]] was taken as being the same as for [[Steel_construction_products#Standard_open_sections|hot rolled beams]] carrying concrete slabs, i.e. 620°C for [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] and 550°C for [[Fire_protecting_structural_steelwork#Sprays|sprays]] and [[Fire_protecting_structural_steelwork#Boards|boards]].
+
For many years, beams with multiple web openings manufactured by splitting and welding hot rolled [[Steel_construction_products#Standard_open_sections|beams and columns]] (castellated and [[Steel_construction_products#Cellular_beams|cellular beams]]), were fire protected on the basis of the [[Calculating_section_factors|section factor]] of the parent section increased by 20%. This guidance was based on the results of a number of tests on castellated beams which showed a small increase in heating rate compared to [[Steel_construction_products#Standard_open_sections|hot rolled sections]]. When a process of manufacturing [[Steel_construction_products#Cellular_beams|cellular beams]] from plates was developed, the 20% rule was retained. The default [[Design_using_structural_fire_standards#Steelwork_strength_in_fire|limiting temperature]] for [[Steel_construction_products#Cellular_beams|cellular beams]] was taken as being the same as for [[Steel_construction_products#Standard_open_sections|hot rolled beams]] carrying concrete slabs, i.e. 620°C for [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] and 550°C for [[Fire_protecting_structural_steelwork#Sprays|sprays]] and [[Fire_protecting_structural_steelwork#Boards|boards]].
  
However, over time, additional testing showed that [[Steel_construction_products#Cellular_beams|cellular beams]] can display complex failure mechanisms in fire.  A much improved understanding of these mechanisms has now been developed and, from this, it has become clear that the assumption that the [[Design_using_structural_fire_standards#Steelwork_strength_in_fire|limiting temperature]] of such beams is the same as for unperforated sections is not correct. Instead it has been shown that the geometry of the beam defines the [[Design_using_structural_fire_standards#Steelwork_strength_in_fire|limiting temperature]] and that every [[Steel_construction_products#Cellular_beams|cellular beams]] needed to be assessed on its own merits. Generalised (or universal) solutions are not appropriate.
+
However, over time, additional testing showed that [[Steel_construction_products#Cellular_beams|cellular beams]] can display complex failure mechanisms in fire.  A much improved understanding of these mechanisms has been developed and it can be shown that the geometry of the beam - particularly the web posts between openings - is of prime importance when determining the [[Design_using_structural_fire_standards#Steelwork_strength_in_fire|limiting temperature]]. The necessary film thickness also depends on the particular product characteristics, so manufacturers generally calculate this for each beam, considering the geometry, loading, and utilization at ambient temperature.  
 
{{#image_template:image=File:Yellow_book_5th_ed.png|caption=The ASFP's Yellow Book<ref name="No8">Fire protection for structural steel in buildings (5th ed). The Association for Specialist Fire Protection.</ref>|align=left|wrap=true|width=200}}
 
{{#image_template:image=File:Yellow_book_5th_ed.png|caption=The ASFP's Yellow Book<ref name="No8">Fire protection for structural steel in buildings (5th ed). The Association for Specialist Fire Protection.</ref>|align=left|wrap=true|width=200}}
 
The great majority of [[Steel_construction_products#Cellular_beams|cellular beams]] are fire protected using [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]]. The Association for Specialist Fire Protection (ASFP) and the Steel Construction Institute (SCI) have developed structural models for beams with circular and rectangular web openings. These models enable the calculation of the [[Design_using_structural_fire_standards#Steelwork_strength_in_fire|limiting temperature]] as a function of beam geometry and load. This can then be used to determine the correct [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|intumescent coating]] thickness for the required fire resistance period, based on a [[Calculating_section_factors|section factor]] calculated using the formula:  
 
The great majority of [[Steel_construction_products#Cellular_beams|cellular beams]] are fire protected using [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]]. The Association for Specialist Fire Protection (ASFP) and the Steel Construction Institute (SCI) have developed structural models for beams with circular and rectangular web openings. These models enable the calculation of the [[Design_using_structural_fire_standards#Steelwork_strength_in_fire|limiting temperature]] as a function of beam geometry and load. This can then be used to determine the correct [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|intumescent coating]] thickness for the required fire resistance period, based on a [[Calculating_section_factors|section factor]] calculated using the formula:  
Line 157: Line 155:
  
 
Some [[Steel_construction_products#Cellular_beams|cellular beam]] manufacturers will also supply [[Design_using_structural_fire_standards#Steelwork_strength_in_fire|limiting temperatures]] for their products.   
 
Some [[Steel_construction_products#Cellular_beams|cellular beam]] manufacturers will also supply [[Design_using_structural_fire_standards#Steelwork_strength_in_fire|limiting temperatures]] for their products.   
The ASFP publishes details of the test protocol that [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coating]] manufacturers must follow if their material is to be used on [[Steel_construction_products#Cellular_beams|cellular beams]]<ref name="No8"></ref>. This has separate parts for testing on beams with circular and rectangular openings. [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|Thin film intumescent coatings]] which are to be used on beams with circular web openings must be tested to that part of the protocol but [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] which are to be used on beams with rectangular openings must be tested to both parts. 
+
The ASFP publishes details of the test protocol that [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coating]] manufacturers must follow if their material is to be used on [[Steel_construction_products#Cellular_beams|cellular beams]]<ref name="No8"></ref>.  
  
Only [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] which have been tested to the ASFP protocol can be used to fire protect [[Steel_construction_products#Cellular_beams|cellular beams]]. The exception to this is where it can be shown that a beam and/or [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coating]] manufacturer have developed their own structural model and design software which specifies particular [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] tested by them and independently third party certified.  
+
Only [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] which have been tested to the ASFP protocol can be used to fire protect [[Steel_construction_products#Cellular_beams|cellular beams]]. The exception to this is where it can be shown that a beam and/or [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coating]] manufacturer have developed their own structural model and design software which specifies particular [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] tested by them and certified by an independent third party.  
  
 
Specifiers should always request confirmation that the performance of [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] intended for use on their project has been tested and assessed for use on beams with web openings as required.  
 
Specifiers should always request confirmation that the performance of [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]] intended for use on their project has been tested and assessed for use on beams with web openings as required.  
  
 
In rare instances, [[Steel_construction_products#Cellular_beams|cellular beams]] are protected by [[Fire_protecting_structural_steelwork#Sprays|sprays]] or [[Fire_protecting_structural_steelwork#Boards|boards]]. Advice on specification of fire protection in this instance is given in the ASFP guidance<ref name="No8"></ref>.
 
In rare instances, [[Steel_construction_products#Cellular_beams|cellular beams]] are protected by [[Fire_protecting_structural_steelwork#Sprays|sprays]] or [[Fire_protecting_structural_steelwork#Boards|boards]]. Advice on specification of fire protection in this instance is given in the ASFP guidance<ref name="No8"></ref>.
<!--THE FOLLOWING TEXT WAS REMOVED 10/7/14 BY JD AS ALL THE NECESSARY INFORMATION WAS IN THE NEW YELLOW BOOK
 
states that a ‘passive rule’ for the fire protection of all [[Steel_construction_products#Cellular_beams|cellular beams]] and castellated sections is permitted, subject to the provisions listed below:
 
*That the [[Calculating_section_factors|section factor]]  is determined by the formula: [[Calculating_section_factors|Section factor]] = 1400/t where t is the web thickness in mm.[Note: in situations where the web thickness varies, this is the bottom web thickness]
 
*That the [[Design_using_structural_fire_standards#Steelwork_strength_in_fire|limiting temperature]] for the [[Steel_construction_products#Cellular_beams|cellular beam]] is determined and declared by the beam manufacturer, or a competent structural engineer, recognised by the Engineering Council. No proposal should be offered where the [[Design_using_structural_fire_standards#Steelwork_strength_in_fire|limiting temperature]] is not provided.
 
*The fire protection product being considered must have been tested and assessed for standard ‘solid’ [[Steel_construction_products#Standard_open_sections|I-section beams]].
 
*The thickness of the fire protection product/system will be determined from the [[Calculating_section_factors|section factor]], the [[Design_using_structural_fire_standards#Steelwork_strength_in_fire|limiting temperature]] , and fire protection product temperature tables, for the appropriate [[Structural_fire_resistance_requirements|fire resistance periods]]. The thickness will then be multiplied by 1.2 to provide a prudent and conservative generic solution.
 
<br>
 
For all materials, where no [[Design_using_structural_fire_standards#Steelwork_strength_in_fire|limiting temperature]] has been provided, the ASFP advise using a  conservative default temperature of 450°C with the proviso that the design engineer is satisfied that this will satisfy all possible modes of structural failure.-->
 
 
Consideration should also be given to [[Design_of_composite_steel_deck_floors_for_fire#Filling_of_voids|filling of voids]] for [[Steel_construction_products#Cellular_beams|cellular beams]].
 
  
 
==Trends in structural fire protection==
 
==Trends in structural fire protection==
The most obvious trend in structural fire protection for steel over the past two decades has been the rise in popularity of [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]]. This has been driven by an intensely competitive industry which has in turn driven R&D. This has created an impetus behind better, cheaper, thinner materials to the point where, in real terms, costs are a fraction of what they were in the 1990s. This has also been helped by the development of [[Fire_protecting_structural_steelwork#Off_site_applied_intumescent_coatings|off-site applied intumescent coatings]] which has given manufacturers a new market.
+
The most obvious trend in structural fire protection for steel over the past three decades has been the rise in popularity of [[Fire_protecting_structural_steelwork#Thin_film_intumescent_coatings|thin film intumescent coatings]]. This has been driven by an intensely competitive industry which has in turn driven further research and development. This has created an impetus to develop more effective, thinner, faster-curing materials to the point where, in real terms, costs are a fraction of what they were in the 1990s.  
 
<gallery caption="Trends in structural fire protection" perrow=2 widths=500px heights=500px>  
 
<gallery caption="Trends in structural fire protection" perrow=2 widths=500px heights=500px>  
 
Image:Trends_in_structural_fire_protection_to_2014_V2.png|
 
Image:Trends_in_structural_fire_protection_to_2014_V2.png|

Latest revision as of 14:37, 15 June 2022

Passive fire protection materials insulate steel structures from the effects of the high temperatures that may be generated in fire. They can be divided into two types, non-reactive, of which the most common types are boards and sprays, and reactive, of which thin film intumescent coatings are the most common example. Thin film intumescent coatings can be either on-site or off-site applied.

               Intumescent coating example 3.png
Thin film intumescent coatings
(Image courtesy of Sherwin-Williams Protective and Marine Coatings)

[top]Intumescent Coatings

Intumescent coatings are paint-like materials which are inert at low temperatures but which provide insulation as a result of a complex chemical reaction at temperatures typically of about 200-250°C. At these temperatures the properties of steel will not be affected. As a result of this reaction the coatings swell and provide an expanded layer of low conductivity char.

Intumescent coatings can be divided into two broad families: thin film and thick film. Thin film materials are either solvent-based or water-based and are mainly used to protect building structures. Thick film intumescent coatings were originally developed for the off-shore and hydrocarbon industries but have been modified for use in buildings.

[top]Thin film intumescent coatings

Thin film intumescent coating systems generally have three components, a primer, a basecoat (the part which reacts in the fire) and a sealer coat. The basecoat usually comprises the following ingredients:

  • A catalyst which decomposes to produce a mineral acid such as phosphoric acid.
  • A carbonific such as starch which combines with the mineral acid to form a large volume of carbonaceous char.
  • A binder or resin which softens at a predetermined temperature.
  • A spumific agent which decomposes together with the melting of the binder, to liberate large volumes of non-flammable gases. These gases include carbon dioxide, ammonia and water vapour. The production of these gases causes the carbonaceous char to swell or foam and expand to provide an insulating layer many times the original coating thickness.


Thin film intumescent coatings are mainly used in buildings where the fire resistance requirements are 30, 60 and 90 minutes. In recent years, a number of products have been developed which can provide 120 minutes fire resistance . They can be applied either on-site or off-site. In general, for structures in a C1 environment (dry internal steelwork), most on-site application is carried out using water-based materials. For more aggressive environments, solvent-based products are commonly applied. Solvent-based materials also tend to be able to cover a wider range of section factors than water-based materials and can be used on-site to protect smaller sections requiring high thicknesses.

Both solvent-based and water-based coatings can be used to achieve attractive surface finishes. If a decorative or bespoke finish is required, this should be included in the specification. Thin film intumescents have the added advantages that they can easily cover complex shapes and post-protection service installation is relatively simple.

Typical expansion ratios are about 50:1, i.e. a 1mm thick coating will expand to about 50mm when affected by heat.

Detailed guidance on the specification and installation of site applied, thin film intumescent coatings is available from the Association for Specialist Fire Protection[1].


[top]Off-site applied intumescent coatings

               Off site application.png
Off-site application

Off-site application usually involves coating the steelwork in a large, well ventilated and heated facility remote from the construction site. Off-site application has a number of distinct advantages:

  • Reduced site programme
  • Improved quality control
  • Reduction in site disruption
  • Cleaner sites
  • Improved site safety
  • Easier servicing installation


Specifiers should be aware that off-site applied thin film intumescent coatings are used mainly for non-aesthetic end uses. Aesthetic finishes are possible, and have been achieved using off-site application but require increased care, particularly when handling the steelwork. Some damage in transit is inevitable, which will need to be repaired; producing a perfect match is difficult.

Applying thin film intumescent coatings off-site is a specialised task. The Association for Specialist Fire Protection publishes a guidance document[2] to assist specifiers. This includes a model specification from which clauses can be taken to put in the specifier’s own contract documents.

Off-site application is more expensive than its on-site equivalent in terms of up-front costs but the advantages can make it more cost-effective overall. Off-site application has a significant market share in the UK.


[top]Thick film intumescent coatings

Thick film intumescent coatings are usually epoxy based and typically have a much higher dry film thickness than thin film alternatives. These materials are tough and durable and were originally developed for use with hydrocarbon fires, where the test heating regime is much more severe than that used for most industrial and commercial applications. A number of manufacturers have modified their materials for use in cellulosic fires. These modified materials are usually used in situations where the benefits of intumescent coatings in terms of appearance, weight and thickness are required but where circumstances are too severe, or maintenance too difficult, to allow the use of thin film materials. Typical examples where thick film coatings may be appropriate include external steel in high rise buildings and exposed marine environments.

Expansion ratios for thick film intumescents are much lower than for thin film materials, typically about 5:1. Aesthetic finishes are possible and it can also be supplied in the form of preformed casings. Thick film intumescent coatings can also be applied off-site.

[top]Boards

               Board and intumescent.png
Interfacing between boards and thin film intumescent coatings is quite common
(Image courtesy of Promat Ltd.)

Boards are widely used for structural fire protection in the UK. They are used both where the protection system is in full view and where it is hidden. They offer the specifier a clean, boxed appearance and have the additional advantages that application is a dry trade and generally have minimal impacts on other activities. Fire protection boards are factory manufactured and have consistent thickness. Board protection can be applied to unpainted steelwork.

There are broadly two families of board protection, lightweight and heavyweight. Lightweight boards are typically 150-250kg/m³ and are not usually suitable for decorative finishes. They are typically used where an aesthetic finish is not required and are cheaper than heavyweight equivalents. Heavyweight boards are usually in the range 700-950kg/m³ and will generally accept decorative finishes. They are typically used where an aesthetic finish is required.

Both types of board may be used in limited external conditions but the advice of the manufacturer should be sought. Detailed guidance on the installation of board protection systems is available from the Association for Specialist Fire Protection[3].


[top]Sprays

               Cementitious spray on beams with openings.jpg
Cementitious spray on beams
(Image courtesy of Promat Ltd.)

Spray protection is extensively used in the United States but is less common in the United Kingdom. It has the advantage that it can be used to cover complex shapes and details and also that costs do not increase significantly with increases in protection thickness. This is because much of the cost of application is in the labour and equipment rather than the cost of the material. Some materials can also be used in external and hydrocarbon fire applications.

Sprays are not suitable when an aesthetic finish is required. Spray application is a wet trade which is likely to have a significant effect on site operations. Overspray is is to be expected, which requires protection of other building elements (and may require complete encapsulation at the edges of the building). Cleaning floors after spray operations is also required. Detailed guidance on the installation of spray protection systems is available from the Association for Specialist Fire Protection[4].

[top]Flexible blanket systems

               Blanket application.png
Flexible blanket system
(Image courtesy of Thermal Ceramics Ltd.)

Flexible fire protection systems have been developed as a response to the need for an easily applied fire protection material which can be used on complex shapes and details but where application is a dry trade. There are a limited number of manufacturers of these products. Fixing of a blanket is shown in the accompanying photograph.

[top]Concrete encasement

               Concrete encasement.png
Concrete encasement of structural steelwork

Until the late 1970s, concrete was by far the most common form of fire protection for structural steelwork. However the introduction of lightweight, proprietary systems such as boards, sprays and thin film intumescent coatings has seen a dramatic reduction in its use. Nevertheless, concrete encasement has its place and it continues to have a small percentage of the fire protection market with other traditional methods such as blockwork encasement. The principal advantage of concrete is durability. It tends to be used where resistance to impact damage, abrasion and weather exposure are important e.g. warehouses, underground car parks and external structures. The principal disadvantages are:

  • Cost - compared to lightweight systems;
  • Space utilisation (large protection thicknesses take up valuable space around columns)
  • Weight.


Information on thickness of concrete encasement for specific periods of fire resistance is published by the Building Research Establishment[5]. It can also be found in BS EN 1994-1-2[6].

[top]Partial protection

Standard fire tests have shown that structural members which are only partially exposed to fire can exhibit substantial levels of fire resistance without applied protection. Methods have been developed to demonstrate 30 and 60 minutes fire resistance. Where higher periods of fire resistance are called for, reduced fire protection thicknesses can be applied to the remaining exposed steelwork since the heated perimeter, and therefore the section factor is less than that for the fully exposed case. See here for more details.

There are five ways in which partial protection can be used:

[top]Block-infilled columns

30 minutes fire resistance can be achieved by the use of autoclaved, aerated concrete blocks cemented between the flanges and tied to the web of rolled sections. Longer fire resistance periods are possible by protecting only the exposed flanges. Guidance is available from the Building Research Establishment[7].


[top]Shelf angle floor beams

               Shelf angle floor beam.png
               

Shelf angle floor beams are beams with angles welded or bolted to the web to support the floor slab. The floor slab protects the top part of the beam from the fire while the bottom part remains exposed. Fire resistance increases as the position of the supporting angle is moved further down the beam and 60 minutes fire resistance is achievable in some instances. Shelf angle floor beams are more commonly bolted rather than welded as shown in the accompanying photograph.

Guidance is available in SCI P126.

[top]Slim floor beams

               Protected Slimflor.png
Protected 'Slim floor' beam with precast concrete planks

There are a number of shallow floor solutions using ‘integrated’ beams. The beams may either be rolled or fabricated, and a number of alternatives are available. One such fabricated beam consists of an H section (usually UC) with a welded bottom plate – this is often called a ‘Slim floor beam’. Others include Ultra Shallow Floor Beams (USFB) from Kloeckner Westok. The common theme is that the beams are asymmetric with a wider bottom flange than top flange to carry the deck slab, which may be either precast concrete (pc) units, or a deep deck composite slab.

A key feature of such shallow floor systems is that almost the whole steel section is protected from the fire by the floor slab and up to 60 minutes fire resistance is achievable without protection to the exposed bottom plate.

Where periods of fire resistance greater than 60 minutes are required, only the exposed bottom flange or plate or the beam requires protection. The section factor is calculated on the basis of the heated perimeter of the bottom flange or plate.

[top]Web infilled columns

Sixty minutes fire resistance can be achieved for columns when normal weight concrete is cast between the flanges and connected by shear connectors attached to the web. The concrete is retained by a web stiffener fixed at the bottom of the connection zone.

The load carrying capacity of the concrete is ignored in the design of the columns but in fire, as the exposed steel weakens at high temperatures, the load carried by the flanges is progressively transferred to the concrete. This provides stability for periods of fire resistance up to 60 minutes . The connection zone is fire protected along with the beam. Guidance is available in the Steel Construction Institute publication SCI P124.


[top]Composite beams and columns with full and partial concrete encasement

               Reinforced column.png
Reinforced column

This is a form of construction which has been introduced by the publication of BS EN 1994-1-2[6], which describes the system and also includes tabulated design guidance. It consists of steel beams and columns in which fire resistance is achieved by the addition of reinforced concrete between the member flanges. Fire resistance periods up to 120 minutes is achievable on columns using this approach and 180 minutes on beams. Guidance is also given on full concrete encasement and up to 240 minutes fire resistance can be achieved.

[top]Protecting cellular beams

               Cellular beam protected.png
A common scene in UK construction. A cellular beam protected using a thin film intumescent coating

For many years, beams with multiple web openings manufactured by splitting and welding hot rolled beams and columns (castellated and cellular beams), were fire protected on the basis of the section factor of the parent section increased by 20%. This guidance was based on the results of a number of tests on castellated beams which showed a small increase in heating rate compared to hot rolled sections. When a process of manufacturing cellular beams from plates was developed, the 20% rule was retained. The default limiting temperature for cellular beams was taken as being the same as for hot rolled beams carrying concrete slabs, i.e. 620°C for thin film intumescent coatings and 550°C for sprays and boards.

However, over time, additional testing showed that cellular beams can display complex failure mechanisms in fire. A much improved understanding of these mechanisms has been developed and it can be shown that the geometry of the beam - particularly the web posts between openings - is of prime importance when determining the limiting temperature. The necessary film thickness also depends on the particular product characteristics, so manufacturers generally calculate this for each beam, considering the geometry, loading, and utilization at ambient temperature.

               Yellow book 5th ed.png
The ASFP's Yellow Book[8]

The great majority of cellular beams are fire protected using thin film intumescent coatings. The Association for Specialist Fire Protection (ASFP) and the Steel Construction Institute (SCI) have developed structural models for beams with circular and rectangular web openings. These models enable the calculation of the limiting temperature as a function of beam geometry and load. This can then be used to determine the correct intumescent coating thickness for the required fire resistance period, based on a section factor calculated using the formula:

Section factor = 1400/t

where t is the web thickness in mm.[Note: in situations where the web thickness varies, this is the bottom web thickness]

Some cellular beam manufacturers will also supply limiting temperatures for their products. The ASFP publishes details of the test protocol that thin film intumescent coating manufacturers must follow if their material is to be used on cellular beams[8].

Only thin film intumescent coatings which have been tested to the ASFP protocol can be used to fire protect cellular beams. The exception to this is where it can be shown that a beam and/or thin film intumescent coating manufacturer have developed their own structural model and design software which specifies particular thin film intumescent coatings tested by them and certified by an independent third party.

Specifiers should always request confirmation that the performance of thin film intumescent coatings intended for use on their project has been tested and assessed for use on beams with web openings as required.

In rare instances, cellular beams are protected by sprays or boards. Advice on specification of fire protection in this instance is given in the ASFP guidance[8].

[top]Trends in structural fire protection

The most obvious trend in structural fire protection for steel over the past three decades has been the rise in popularity of thin film intumescent coatings. This has been driven by an intensely competitive industry which has in turn driven further research and development. This has created an impetus to develop more effective, thinner, faster-curing materials to the point where, in real terms, costs are a fraction of what they were in the 1990s.


[top]Case studies


[top]References

  1. ASFP Technical Guidance Document - TGD 11. Code of practice for the specification & on-site installation of intumescent coatings for fire protection of structural steelwork
  2. ASFP Technical Guidance Document - TGD 16. Code of Practice for Off-site Applied Thin Film Intumescent Coatings
  3. ASFP Technical Guidance Document - TGD 14. Code of practice for the installation and inspection of board systems for the fire protection of structural steel work
  4. ASFP Technical Guidance Document - TGD 15. Code of practice for the installation & inspection of sprayed non-reactive coatings for the fire protection of structural steelwork
  5. Guidelines for the Construction of Fire Resisting Structural Elements. Building Research Establishment.
  6. 6.0 6.1 BS EN 1994-1-2: 2005+A1:2014, Eurocode 4. Design of composite steel and concrete structures. General rules. Structural fire design. BSI
  7. BRE Digest 317. Fire resistant steel structures: free-standing blockwork-filled columns and stanchions. Building Research Establishment